THAT YOU WERE WARNED ABOUT
Unforeseen circumstances to blame
for Texas electricity fiasco
During an emergency board meeting of the Electric Reliability Council of Texas (ERCOT), Bill Magness, ERCOT CEO, outlined the events that took place between February 14 and 18 that ultimately led to the humanitarian crisis that many Texas residents are still in the midst of now.
An oversimplified view of the Texas electricity market
First of all, it’s necessary to understand how the electricity market works in Texas. It’s a free market. The players in the market are the electricity generators and the utilities who control the poles and wires and serve the customers. Then there is the system operator that works between the two. That system operator is ERCOT. (The customers buy their electricity from retail electricity providers who buy it from the generators themselves but that’s beside the point for this article.)
Think of ERCOT as an orchestra conductor, directing instruments to turn up or turn down as needed to keep the grid in balance. (Remember that with electricity, you have to keep supply and demand perfectly balanced at all times.)
Because it’s a free market with little regulation, the conductor (ERCOT) does not have the authority to impose fees or set rules for the generators. For example, ERCOT is not allowed to tell a particular generator that they won’t be able to play in the orchestra if they don’t do XYZ. Instead, ERCOT relies on market prices to serve as motivation to keep those generator plants humming along as much as they can. That way, if and when some generators can’t provide energy (there is less supply), the price for electricity goes up so those that CAN provide, do and reap the rewards of being online at the right time. In fact, it is these “scarcity events” that help drive the development of new generation, so in general, they are not a bad thing.
Overall, the market works very well in normal conditions. Most Texans will tell you they have very low electricity prices as a result of being deregulated.
At certain times, however, there just isn’t enough supply, no matter how high the price goes, and that’s when ERCOT’s only tool is to shed demand. To do that, it orders the utilities to turn off power to certain customers based on the number of megawatts their customers use (see chart). Utilities have plans for this and understand how they will do that fairly and in the most equitable way possible. For example, they don’t want to shut down hospitals or other critical care facilities. In a normal emergency, this load shed can be distributed across a service territory, so a certain subset of customers only lose power for a couple of hours, then they are turned back on and another neighborhood goes dark for a couple of hours.
But what happened in Texas on February 14-18, 2021 was an event that was not foreseen and could not have been predicted mostly because of the sheer numbers involved. Because the temps were so cold and so many generators couldn’t generate electricity (another article for another time) ERCOT turned to rolling blackouts. But, the rolling blackouts that should normally only last a couple of hours turned into multiple days and that led to all kinds of disastrous consequences.
February 2011 compared to February 2021
While many stakeholders are crying foul because the event was precedented by a similar cold snap in February 2011 that led to rolling blackouts — and there are some similarities to the events of February 1-5, 2011 — the numbers are staggeringly different. Let’s look:
2011 | 2021 | |
---|---|---|
Maximum generation capacity forced out at any given time (MW) | 14,702 | 52,277 |
Generation forced out one hour before the start of EEA3 (MW) | 1,182 | 2,489 |
Cumulative generation capacity forced out through the event | 29,729 | 46,249 |
Cumulative number of generators unable to perform throughout the event | 193 | 356 |
Cumulative gas generation de-rated due to supply issues | 1,282 | 9,323 |
Lowest frequency | 59.58 | 59.30 |
Maximum load shed requested (MW) | 4,000 | 20,000 |
Duration of load shed requested (hours) | 7.5 | 70.5 |
Estimated peak load without load shed | 59,000 | 76,818 |
The numbers that are most striking are load shed and duration. This time around, ERCOT requested 5X the amount of load be shed and for almost 10X longer. And that doesn’t correlate with the temperature. It was not 10X colder. It wasn’t even 5X colder. And the cold didn’t last 10X as long, it didn’t even last 5X as long.
Look at the numbers:
Number of Consecutive Hours Below Freezing 2011 VS 2021
Location | 2011 | 2021 |
---|---|---|
DFW | 101 | 140 |
Austin | 69 | 162 |
Houston | 34 | 44 |
Finally, in his report, Magness outlined what recommendations were implemented after the 2011 event. He said the entity made the following modifications:
- Implemented the Seasonal Assessment of Resource Adequacy report that includes an analysis for extreme winter weather.
- Began a resource weatherization process that includes an annual workshop, review of resource weatherization plans and spot checks of facilities.
- Added additional staff (Shift Engineer and Resource Reliability Desk) in the control room.
- Modified the Ancillary Services procurement to allow additional procurement in anticipation of severe weather.
- Established the Gas Electric Working Group and created a notification procedure for QSEs to notify ERCOT if there are anticipated fuel restrictions.
- Modified the survey sent to natural gas generators that collects fuel switching capability for some resources in preparation for each winter season.
- Changed the rules and processes for withdrawing approval of resource outages in anticipation of severe weather.
It’s also important to understand what would happen if they didn’t shed that load and the grid completely failed. In this case, all power to all facilities would be off – no cell phones, no hospitals, no banks, nothing. And to get the grid back up and running after an event like that would take weeks.
No doubt, experts will be studying the events that took place February 14-18, 2021 for a very long time. ERCOT is still awaiting generator reports that will help it begin to dissect why so many electricity generators were unable to perform. They know that lack of weatherization played a role, but they would like a full report. And, there’s the market aspect to contend with. When those electricity prices shot up to $9000 per MWh (the market cap), those who still were receiving electricity were hit with massive bills, which could ultimately affect every single customer in Texas.
Originally published on power-eng.com
No comments:
Post a Comment